pagina

COMPLIANCE WITH NOM-003-SEMARNAT-1997

Official Mexican standard NOM-003-SEMARNAT-1997, which establishes the maximum permissible limits of contaminants for treated wastewater that is reused in public services. (Published in the Official Gazette of the Federation on September 21, 1998)

MAXIMUM PERMISSIBLE LIMITS OF CONTAMINANTS
REUSE TYPE
MONTHLY AVERAGE
Fecal coliforms
NMP/100 ml
Eggs of
Helminth (h/l)
Fats and
oils mg/l
DBO5 mg/l SST mg/l
PUBLIC SERVICES
WITH DIRECT CONTACT
240 ≥ 1 15 20 20
PUBLIC SERVICES
WITH INDIRECT CONTACT
or OCCASIONAL
1,000 ≥ 5 15 30 30

KWT PTARs are designed to treat water to the most demanding level of the official Mexican standard.

PLANTS FOR COMPLIANCE WITH NOM-001-SEMARNAT-2022

That establishes the maximum permissible limits of contaminants in the discharge of wastewater and national assets

Parameters (*)
(milligrams per liter,
except when
specify)
Rivers, streams,
channels, drains
Reservoirs,
lakes and lagoons
Mexican marine
zones and estuaries
Floor
Area irrigation
green
Infiltration and
other risks
P.M P.D V.I P.M P.D V.I P.M P.D V.I P.M P.D V.I P.M P.D V.I
Temperature (℃) 35 35 35 35 35 35 40 40 40 35 35 35 35 35 35
Fats and oils 15 18 21 15 18 21 15 18 21 15 18 21 15 18 21
Suspended Solids
Totals
60 72 84 20 24 28 20 24 28 30 36 42 100 120 140
Chemical Demand for
Oxygen
150 180 210 100 120 140 85 100 120 60 62 84 150 180 210
Organic Carbon
Total*
38 45 53 25 30 35 21 25 30 15 18 21 38 45 53
Total Nitrogen 25 30 35 20 25 30 25 30 35 NA NA NA NA NA NA
Total Phosphorus 15 18 21 12 15 18 15 18 21 NA NA NA NA NA NA
Helminth eggs
(eggs/litre)
NA NA NA NA NA NA NA NA NA 1
Escherichia coli,
(NMP/100 ml)
1000 1200 1400 1000 1200 1400 1000 1200 1400 1000 1200 1400 1000 1200 1400
Fecal enterococci**
(NMP/100 ml)
1000 1200 1400 1000 1200 1400 1000 1200 1400 1000 1200 1400 1000 1200 1400
pH
(UpH)
6.5 - 8.5
True color 15% purity
Acute toxicity
(UT)
Less than or equal to 5

Enviar mensaje por WhatsApp